ELEMENT 35/220…240/800 CS L

Product family benefits
  • Small housing design
  • Flexible current setting (DIPswitch – 4 currents)
  • Enhanced safety due to overload, overtemperature, short-circuit protection
Areas of application
  • Linear lighting for office, school and public areas
  • Suitable for luminaires of protection class I

Technical Data

Electrical data

Nominal input voltage

220…240 V

Mains frequency

50/60 Hz

Input voltage AC

198…264 V

Current set

DipSwitch

Power factor λ

0.96

Full load at 230 V/50 Hz

Efficiency in full-load

88 %

Device power loss

5.24 W

At 230 V

Inrush current

12.5 A

twidth = 180 μs typical (measured at 50 % Ipeak)

Max. ECG no. on circuit breaker 10 A (B)

16

Max. ECG no. on circuit breaker 10 A (C)

30

Max. ECG no. on circuit breaker 16 A (B)

28

Max. ECG no. on circuit breaker 16 A (C)

45

Surge capability (L/N-Ground)

2 kV

Surge capability (L-N)

1 kV

Nominal output voltage

23…51 V

At 500/600mA

Nominal output current

500 / 600 / 700 / 800 mA

±7.5%

Output ripple current (100 Hz)

< 30 %

Ripple average at 100 Hz

Output PSTLM

≤1

Output SVM

≤0.7

Nominal output power

11.5…40.8 W

Maximum output power

40.8 W

Galvanic isolation

SELV

Total harmonic distortion

< 20 %

At full load, 230 V, 50 Hz / see graphs

Default output current

800 mA

Output current tolerance

±7.5 %

U-OUT (working voltage)

< 60 V

Dimensions & weight

Mounting hole spacing, length

200.0 mm

Product weight

140.00 g

Cable cross-section, input side

0.5…1.5 / 0.75…1.5 mm²

Solid or flexible leads

Cable cross-section, output side

0.5…1.5 / 0.75…1.5 mm²

Solid or flexible leads

Wire preparation length, input side

8.5…9.5 mm

Wire preparation length, output side

8.5…9.5 mm

Height

21.0 mm

Width

30.0 mm

Length

210.0 mm

Colors & materials

Casing material

Metal

Temperatures & operating conditions

Ambient temperature range

-20…+50 °C

Maximum temperature at tc test point

75 °C

Max.housing temperature in case of fault

110 °C

Temperature range at storage

-40…+85 °C

Permitted rel. humidity during operation

5…85 %

Non-condensing

Lifespan

ECG lifetime

35000 / 50000 h

At maximum Tc = 75°C / 10% failure rate / At Tc = 65°C / 10% failure rate

Capabilities

Dimmable

No

Overheating protection

Automatic reversible

Overload protection

Automatic reversible

Short-circuit protection

Automatic reversible

No-load proof

Yes

Max. cable length to lamp/LED module

2.0 m

Output wires must be routed as close as possible to each other

Suitable for fixtures with prot. class

I

Number of channels

1

Programming

Programming device

DIPswitch

Certificates & standards

Approval marks – approval

CE / ENEC 05 / EAC / BIS / RCM / CCC

Standards

Acc. to IEC 61347-1/Acc. to EN 61347-2-13/Acc. to EN 62384/Acc. to EN 61000-3-2/Acc. to EN 61000-3-3/Acc. to EN 61547

Type of protection

IP20

Logistical data

Commodity code

85044083900

Environmental information


Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)

Date of Declaration

25-04-2022

Primary Article Identifier

4052899553132

Declaration No. in SCIP database

In work

Packaging information

EAN

Unit

Piece

Dimension l x w x h

Weight

Volume

4052899553132 UNV

Unpacked

1 210mm x 30mm x 21mm 140.00g 0.13dm³
4052899553149 VS

Shipping box

20 228mm x 138mm x 160mm 3078.00g 5.03dm³

Downloads

Information about Family

Perfect price/feature ratio - standard lighting needs for basic pricing.

The ELEMENT SELV driver comes in small housing of only 210 mm and offers a high efficiency of up to 90% and flexibility in current setting by DIPSwitch (4). It is an optimized price/performance driver solution.
Product family features
  • Line frequency: 50 Hz | 60 Hz
  • Supply voltage: 220…240 V
  • Lifetime: up to 50,000 h (temperature at Tc max. = -10 °C, max 10% failure rate)
  • SELV driver
Ecodesign regulation information:
Intended for use with LED modules.
The forward voltage of the LED light source shall be within the defined operating window of the control gear in all operating conditions including dimming if applicable.

Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.

Products

Sort by:
Product
Nominal output voltage
Nominal output current
Length
Width
Height
Data sheet
ELEMENT 35/220…240/800 CS L
23…51 V 500 / 600 / 700 / 800 mA 210.0 mm 30.0 mm 21.0 mm
ELEMENT 55/220…240/1200 CS L
23…51 V 920 / 1050 / 1075 / 1200 mA 210.0 mm 30.0 mm 21.0 mm