IT FIT 15/220 240/700 CS I
- Small housing for flexible luminaire designs
- Flexible current selection via DIP switch
- Reversible overtemperature, overload, short-circuit and open-circuit protection
- Extra small design for downlights, spotlights and other indoor luminaries
- Suitable for luminaires of protection classes I and II
- Suitable for indoor SELV installations
Technical Data
Electrical data
Nominal input voltage
220 240 V
Mains frequency
50/60 Hz
Input voltage AC
198 264 V
Total harmonic distortion
< 10 %
Power factor λ
0.90C 0.95
Efficiency in full-load
86 %
Protective conductor current
<0.7 mA
Inrush current
< 10 A
Max. ECG no. on circuit breaker 10 A (B)
51
Max. ECG no. on circuit breaker 10 A (C)
51
Max. ECG no. on circuit breaker 16 A (C)
82
Max. ECG no. on circuit breaker 16 A (B)
82
Surge capability (L/N-Ground)
2 kV
Surge capability (L-N)
1 kV
Nominal output voltage
11 21 V
U-OUT (working voltage)
60 V
Nominal output current
550 / 600 / 650 / 700 mA
Output current tolerance
±7.5 %
Default output current
700 mA
Output ripple current (100 Hz)
< 5 %
Output PSTLM
≤1
Output SVM
≤0.4
Nominal output power
6.05 14.7 W
Maximum output power
14.7 W
Galvanic isolation
SELV
Galvanic isolation primary/secondary
SELV
Current set
DipSwitch
Dimensions & weight
Mounting hole spacing, length
89.4 mm
Mounting hole spacing, width
22.0 mm
Product weight
56.00 g
Cable cross-section, input side
0.5 1.5 / 0.75 1.5 mm²
Cable cross-section, output side
0.5 1.5 / 0.75 1.5 mm²
Wire preparation length, input side
7 8 mm
Wire preparation length, output side
7 8 mm
Length
104.0 mm
Width
30.0 mm
Height
26.0 mm
Colors & materials
Casing material
Plastic
Temperatures & operating conditions
Ambient temperature range
-20 +50 °C
Maximum temperature at tc test point
80 °C
Max.housing temperature in case of fault
110 °C
Temperature range at storage
-40 +85 °C
Permitted rel. humidity during operation
5 85 %
Lifespan
ECG lifetime
50000 h
Additional product data
Encapsulated
No
Capabilities
Dimmable
No
Overheating protection
Automatic reversible
Overload protection
Automatic reversible
Short-circuit protection
Automatic reversible
No-load proof
Yes
Intended for no-load operation
No
Max. cable length to lamp/LED module
2.0 m
Suitable for fixtures with prot. class
I / II
Type of connection, input side
Push terminal
Type of connection, output side
Push terminal
Number of channels
1
Suitable for through-wiring
No
Control interface
-
Programming
Programming device
DIPswitch
Certificates & standards
Approval marks approval
ENEC 05 / CCC / CE / RCM
Standards
Acc. to IEC 61347-1/Acc. to IEC 61347-2-13/Acc. to IEC 62384/Acc. to IEC 61000-3-2/Acc. to IEC 61000-3-3/Acc. to IEC 61547
Type of protection
IP20
Protection class
II
Logistical data
Commodity code
85044083900
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
29-05-2023
Primary Article Identifier
4062172199322
Candidate List Substance 1
Lead
CAS No. of substance 1
7439-92-1
Safe Use Instruction
The identification of the Candidate List substance is sufficient to allow safe use of the article.
Declaration No. in SCIP database
a3d39858-0cb2-4619-aba4-afc5e626d767
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4062172199322 |
UNV
| 1 | 104mm x 30mm x 26mm | 56.00g | 0.08dm³ |
4062172199339 |
VS
| 20 | 220mm x 162mm x 75mm | 1205.00g | 2.67dm³ |
Downloads
Data sheets
Information about Family
- Supply voltage: 220 240 V
- Line frequency: 50 Hz | 60 Hz
- Line voltage: 198 264 V
- According to EN 61347-1, 61347-2-13, 62384
- RI suppression according to CISPR 15
- Line harmonics according to IEC 61000-3-2
- Immunity according to IEC 61547
Intended for use with LED modules.
The forward voltage of the LED light source shall be within the defined operating window of the control gear in all operating conditions including dimming if applicable.
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|---|
![]() |
IT FIT 4/220
240/400 CS I
|
2.5 10 V | 100 / 200 / 300 / 400 mA | 104.0 mm | 30.0 mm | 26.0 mm | ||
![]() |
IT FIT 7/220
240/700 CS I
|
2.5 11 V | 350 / 400 / 450 / 500 / 550 / 600 / 650 / 700 mA | 104.0 mm | 30.0 mm | 26.0 mm | ||
![]() |
IT FIT 11/220
240/500 CS I
|
11 21 V | 350 / 400 / 450 / 500 mA | 104.0 mm | 30.0 mm | 26.0 mm | ||
![]() |
IT FIT 15/220
240/700 CS I
|
11 21 V | 550 / 600 / 650 / 700 mA | 104.0 mm | 30.0 mm | 26.0 mm |