OT FIT 55/220 240/1A0 CS L G2
- Flexible current setting (DIPswitch 4 currents)
- Lifetime: up to 100,000 h (temperature at Tc = 65 °C, max. 10 % failure rate)
- High efficiency
- High quality of light thanks to low output ripple current
- Fulfill safety requirement due to overload, overtemperature, Hot Plug protection
- Linear lighting for office, education, industry, storage areas and retail
- Installation in emergency lighting systems according to IEC 61347-2-13, appendix J
- Suitable for luminaires of protection class I
Technical Data
Electrical data
Nominal input voltage
220 240 V
Mains frequency
0/50/60 Hz
Input voltage AC
198 264 V
Current set
DipSwitch
Input voltage DC
176 276 V
Total harmonic distortion
< 10 %
Power factor λ
0.98
Device power loss
7.0 W
Inrush current
20 A
Max. ECG no. on circuit breaker 10 A (B)
16
Max. ECG no. on circuit breaker 16 A (B)
25
Max. ECG no. on circuit breaker 25 A (B)
-
Surge capability (L/N-Ground)
2 kV
Surge capability (L-N)
1 kV
Nominal output voltage
27 51 V
U-OUT (working voltage)
< 60 V
Nominal output current
800 / 900 / 975 / 1050 mA
Output current tolerance
±7.5 %
Output ripple current (100 Hz)
< 5 %
Output PSTLM
≤1
Output SVM
≤0.4
Nominal output power
21.6 53.6 W
Galvanic isolation
SELV
Galvanic isolation primary/secondary
-
Default output current
1000 mA
Protective conductor current
2.0 mA
Dimensions & weight
Mounting hole spacing, length
270.0 mm
Product weight
217.00 g
Cable cross-section, input side
0.5 1.5 mm²
Cable cross-section, output side
0.5 1.5 mm²
Wire preparation length, input side
8.5 9.5 mm
Wire preparation length, output side
8.5 9.5 mm
Height
21.0 mm
Width
30.0 mm
Length
280.0 mm
Colors & materials
Casing material
Metal
Temperatures & operating conditions
Ambient temperature range
-25 +50 °C
Maximum temperature at tc test point
80 °C
Max.housing temperature in case of fault
110 °C
Temperature range at storage
-25 85 °C
Permitted rel. humidity during operation
5 85 %
Lifespan
ECG lifetime
50000 / 100000 h
Capabilities
Dimmable
No
Overheating protection
Automatic reversible
Overload protection
Non-reversible
Short-circuit protection
Automatic reversible
No-load proof
Yes
Max. cable length to lamp/LED module
2.0 m
Suitable for fixtures with prot. class
I
Type of connection, output side
Push terminal
Number of channels
1
Programming
Programming device
DIPswitch
Certificates & standards
Approval marks approval
CE / EL / ENEC 05 / EAC / CCC / RCM / BIS
Standards
Acc. to EN 61347-1/Acc. to EN 61347-2-13/Acc. to EN 62384/Acc. to EN 61000-3-2/Acc. to EN 61000-3-3/Acc. to EN 61547
Protection class
I
Type of protection
IP20
Logistical data
Commodity code
850440839000
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
14-04-2022
Primary Article Identifier
4052899522558
Candidate List Substance 1
Lead
CAS No. of substance 1
7439-92-1
Safe Use Instruction
The identification of the Candidate List substance is sufficient to allow safe use of the article.
Declaration No. in SCIP database
cc7f740d-bde9-4c31-b89e-d08b10f41854
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4052899522558 |
UNV
| 1 | 280mm x 30mm x 21mm | 217.00g | 0.18dm³ |
4052899522565 |
VS
| 20 | 303mm x 159mm x 101mm | 4659.00g | 4.87dm³ |
Downloads
Data sheets
Information about Family
Some benefits of this product are its efficiency which goes up to 90%, its long lifetime and guarantee. It is also flexible in its current setting thanks to 4 DIPSwitches and due to a low ripple the lighting quality is improved. This device is also suitable for emergency lighting units.
- Line frequency: 0 Hz | 50 Hz | 60 Hz
- Versatile scope of application due to output power range of up to 75 W
- Supply voltage: 220 240 V
- Available with output current range: up to 1,400 mA
- SELV system
Intended for use with LED modules.
The forward voltage of the LED light source shall be within the defined operating window of the control gear in all operating conditions including dimming if applicable.
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|---|
![]() |
OT FIT 35/220
240/700 CS L G2
|
27 51 V | 500 / 600 / 650 / 700 mA | 280.0 mm | 30.0 mm | 21.0 mm | ||
![]() |
OT FIT 55/220
240/1A0 CS L G2
|
27 51 V | 800 / 900 / 975 / 1050 mA | 280.0 mm | 30.0 mm | 21.0 mm | ||
![]() |
OT FIT 75/220
240/1A4 CS L G2
|
27 51 V | 1100 / 1200 / 1300 / 1400 mA | 360.0 mm | 30.0 mm | 21.0 mm |