QT-FIT5 1X14 35
- Long lamp life
- No adverse effect from frequent on/off switching
- Automatic restart after lamp replacement
- Perfect lamp start for applications with motion sensors
- VDE/VDE EMC certified system
- Very high energy efficiency due to cut-off technology
- Open-plan offices, corridors and storage rooms
- Public buildings
- Strip lighting
- Suitable for luminaires of protection class I
- Modernization of existing systems
Technical Data
Electrical data
Input voltage AC
198 264 V
Nominal voltage
220 240 V
Mains frequency
50 60 Hz
Input voltage DC
185 264 V
Maximum output power
35 W
Efficiency in full-load
93 %
Operating frequency
40 50 kHz
Max. ECG no. on circuit breaker 10 A (B)
17
Max. ECG no. on circuit breaker 16 A (B)
28
Inrush current
24 A
Light technical data
Starting time
2.0 s
Dimensions & weight
Length
280.0 mm
Width
30.0 mm
Height
21.0 mm
Mounting hole spacing, length
270.0 mm
Product weight
160.00 g
Cable cross-section, output side
0.5 1.5 mm²
Cable cross-section, input side
0.5 1.5 mm²
Temperatures & operating conditions
Ambient temperature range
-15 +50 °C
Permitted rel. humidity during operation
5 85 %
Lifespan
ECG lifetime
50000 h
Additional product data
Suitable for lamp power (1 lamp)
14 35 W
Capabilities
End of lamp life safety shutdown
EOL T.2
Suitable for emergency lighting
No
Suitable for fixtures with prot. class
I
Max. cable length to lamp/LED module
2.0 m / 1.0 m
Intended for no-load operation
No
Dimmable
No
Certificates & standards
Approval marks approval
VDE / ENEC 10 / VDE-EMC
EEI Energy Label
A2
Standards
Acc. to EN 61547/IEC 61547/Acc. to EN 61347-2-3/IEC 61347-2-3/Acc. to EN 61000-3-2/IEC 61000-3-2/Acc. to EN 55015:2006 + A1:2007 + A2:2009
Protection class
I
Type of protection
IP20
Logistical data
Commodity code
85041080900
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
26-05-2023
Primary Article Identifier
4008321971234
Candidate List Substance 1
Lead
CAS No. of substance 1
7439-92-1
Safe Use Instruction
The identification of the Candidate List substance is sufficient to allow safe use of the article.
Declaration No. in SCIP database
5e1c99a2-37e3-4677-b185-1b7260edc069
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4008321971234 |
UNV
| 1 | 280mm x 30mm x 21mm | 160.00g | 0.18dm³ |
4008321971241 |
VS
| 20 | 305mm x 161mm x 104mm | 3377.00g | 5.11dm³ |
Downloads
Data sheets
Lamp-ECG Combination
HE 14 W
Nominal current
0.08 A
Nominal wattage + Power loss
16.00 W
Power factor λ [PIM]
0.95
Luminous flux at 35 °C
1200 lm
Number of lighting outlets
1
HE 21 W
Nominal current
0.11 A
Nominal wattage + Power loss
23.00 W
Power factor λ [PIM]
0.95
Luminous flux at 35 °C
1900 lm
Number of lighting outlets
1
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
50 °C
ECG_2.2 Tc point temperature for lifespa
55 °C
ECG_2.3 Tc point temperature for lifespa
65 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
100000 h
ECG_3.3 Temperature dependent lifespan
100000 h
HE 28 W
Nominal current
0.14 A
Nominal wattage + Power loss
31.00 W
Power factor λ [PIM]
0.96
Luminous flux at 35 °C
2600 lm
Number of lighting outlets
1
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
50 °C
ECG_2.2 Tc point temperature for lifespa
55 °C
ECG_2.3 Tc point temperature for lifespa
65 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
100000 h
ECG_3.3 Temperature dependent lifespan
100000 h
HE 35 W
Nominal current
0.17 A
Nominal wattage + Power loss
38.00 W
Power factor λ [PIM]
0.97
Luminous flux at 35 °C
3200 lm
Number of lighting outlets
1
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
50 °C
ECG_2.2 Tc point temperature for lifespa
60 °C
ECG_2.3 Tc point temperature for lifespa
65 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
100000 h
ECG_3.3 Temperature dependent lifespan
90000 h
Information about Family
- Supply voltage: 220 240 V
- Line voltage: 198 264 V
- Line frequency: 50 Hz | 60 Hz
- Lamp start with optimum filament preheating
- Energy Efficiency Index EEI: A2
- Automatic shutdown of defective lamps and at end of life (EoL T.2)
- Lamp operation: to EN 60929
- Safety: to EN 61347-2-3
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|---|
![]() |
QT-FIT5 1X14
35
|
21.0 mm | No | 50000 h | 280.0 mm | 30.0 mm | ||
![]() |
QT-FIT5 2X14
35
|
21.0 mm | No | 280.0 mm | 30.0 mm | |||
![]() |
QT-FIT5 3X14,4X14
|
21.0 mm | No | 50000 h | 280.0 mm | 40.0 mm | ||
![]() |
QT-FIT5 1X49
|
21.0 mm | No | 50000 h | 280.0 mm | 30.0 mm | ||
![]() |
QT-FIT5 2X49
|