QT-FIT5 2X14 35
Product family benefits
- Long lamp life
- No adverse effect from frequent on/off switching
- Automatic restart after lamp replacement
- Perfect lamp start for applications with motion sensors
- VDE/VDE EMC certified system
- Very high energy efficiency due to cut-off technology
Areas of application
- Open-plan offices, corridors and storage rooms
- Public buildings
- Strip lighting
- Suitable for luminaires of protection class I
- Modernization of existing systems
Technical Data
Electrical data
Nominal voltage
220 240 V
Mains frequency
50 60 Hz
Input voltage DC
198 264 V
Maximum output power
2 x 35 W
Efficiency in full-load
91 %
Operating frequency
40 50 kHz
Light technical data
Starting time
2.0 s
Dimensions & weight
Length
280.0 mm
Width
30.0 mm
Height
21.0 mm
Mounting hole spacing, length
270.0 mm
Product weight
181.00 g
Cable cross-section, input side
0.5 1.5 mm²
Cable cross-section, output side
0.5 1.5 mm²
Temperatures & operating conditions
Ambient temperature range
-15 +50 °C
Permitted rel. humidity during operation
5 85 %
Additional product data
Suitable for lamp power (2 lamps)
14 35 W
Capabilities
Suitable for emergency lighting
No
Suitable for fixtures with prot. class
I
End of lamp life safety shutdown
EOL T.2
Intended for no-load operation
No
Max. cable length to lamp/LED module
2.0 m / 1.0 m
Dimmable
No
Certificates & standards
Approval marks approval
VDE / ENEC 10 / VDE-EMC
EEI Energy Label
A2 BAT
Standards
Acc. to EN 61347-2-3/IEC 61347-2-3/Acc. to EN 55015:2006 + A1:2007 + A2:2009/Acc. to EN 61000-3-2/IEC 61000-3-2/Acc. to EN 61547/IEC 61547
Type of protection
IP20
Protection class
I
Logistical data
Commodity code
850410809000
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
14-04-2023
Primary Article Identifier
4008321971258
Candidate List Substance 1
Lead
CAS No. of substance 1
7439-92-1
Safe Use Instruction
The identification of the Candidate List substance is sufficient to allow safe use of the article.
Declaration No. in SCIP database
5cf3d820-15df-429b-9da4-9cf55f4f2e00
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4008321971258 |
UNV
| 1 | 280mm x 30mm x 21mm | 181.00g | 0.18dm³ |
4008321971265 |
VS
| 20 | 303mm x 101mm x 159mm | 3786.00g | 4.87dm³ |
Downloads
Data sheets
Lamp-ECG Combination
HE 14 W
Nominal current
0.14 A
Nominal wattage + Power loss
32.00 W
Power factor λ [PIM]
0.98
Luminous flux at 35 °C
1200 lm
Number of lighting outlets
2
HE 21 W
Nominal current
0.22 A
Nominal wattage + Power loss
46.00 W
Power factor λ [PIM]
0.98
Luminous flux at 35 °C
1900 lm
Number of lighting outlets
2
HE 28 W
Nominal current
0.26 A
Nominal wattage + Power loss
63.00 W
Power factor λ [PIM]
0.98
Luminous flux at 35 °C
2600 lm
Number of lighting outlets
2
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
55 °C
ECG_2.2 Tc point temperature for lifespa
65 °C
ECG_2.3 Tc point temperature for lifespa
70 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
100000 h
ECG_3.3 Temperature dependent lifespan
70000 h
HE 35 W
Nominal current
0.35 A
Nominal wattage + Power loss
78.00 W
Power factor λ [PIM]
0.98
Luminous flux at 35 °C
3300 lm
Number of lighting outlets
2
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
60 °C
ECG_2.2 Tc point temperature for lifespa
70 °C
ECG_2.3 Tc point temperature for lifespa
75 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
80000 h
ECG_3.3 Temperature dependent lifespan
50000 h
Information about Family
When it comes to ECG installation, the QUICKTRONIC FIT 5 ECG is a great option if you are using T5 lamps. Available in a choice of specifications, key features include lamp start with optimal filament preheating, an energy efficiency index of A2, and automatic shutoff of defective lamps and at end of life. Use it with luminaires of protection class I, for open-plan office lighting, corridors, storage rooms, public buildings and strip lighting. Benefits include long lamp life, the ability to withstand frequent on/off switching without harm, automatic restart after lamp replacement and very high levels of efficiency thanks to the units cutoff technology. If your application uses motion sensors, this ECG will give perfect lamp start, and its VDE/VDE EMC certified system gives reliability and safety assurances.
Product family features
- Supply voltage: 220 240 V
- Line voltage: 198 264 V
- Line frequency: 50 Hz | 60 Hz
- Lamp start with optimum filament preheating
- Energy Efficiency Index EEI: A2
- Automatic shutdown of defective lamps and at end of life (EoL T.2)
- Lamp operation: to EN 60929
- Safety: to EN 61347-2-3
Ecodesign regulation information:
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|---|
![]() |
QT-FIT5 1X14
35
|
21.0 mm | No | 50000 h | 280.0 mm | 30.0 mm | ||
![]() |
QT-FIT5 2X14
35
|
21.0 mm | No | 280.0 mm | 30.0 mm | |||
![]() |
QT-FIT5 3X14,4X14
|
21.0 mm | No | 50000 h | 280.0 mm | 40.0 mm | ||
![]() |
QT-FIT5 1X49
|
21.0 mm | No | 50000 h | 280.0 mm | 30.0 mm | ||
![]() |
QT-FIT5 2X49
|