QTi 1X14/24/21/39 GII

Product family benefits
  • Long lamp life
  • No adverse effect from frequent on/off switching
  • Automatic restart after lamp replacement
  • Perfect lamp start for applications with motion sensors
  • VDE/VDE EMC certified system
  • Very high energy efficiency due to cut-off technology
Areas of application
  • Emergency lighting systems acc. to EN 50172 / DIN VDE 0108-100
  • Industry
  • Open-plan offices, corridors and storage rooms
  • Public buildings
  • Sports halls and factories
  • Strip lighting
  • Suitable for emergency lighting (DC operation)
  • Modernization of existing systems
  • Suitable for luminaires of protection classes I and II

Technical Data

Electrical data

Input voltage AC

198…264 V

Nominal voltage

220…240 V

Mains frequency

50…60 Hz

Input voltage DC

176…276 V

Maximum output power

39 W

Efficiency in full-load

91 %

at 230 V, 50 Hz

Operating frequency

42…85 kHz

Max. ECG no. on circuit breaker 10 A (B)

17

Type B

Max. ECG no. on circuit breaker 16 A (B)

28

Type B

Inrush current

24 A

Light technical data

Starting time

1.0 s

If there is a temporary interruption in the power supply (< 0.5 s), the lamp will start within 0.3 s

Dimensions & weight

Length

360.0 mm

Width

30.0 mm

Height

21.0 mm

Mounting hole spacing, length

350.0 mm

Product weight

210.25 g

Temperatures & operating conditions

Ambient temperature range

-20…+50 °C

Permitted rel. humidity during operation

5…85 %

Maximum 56 days/year at 85 %

Lifespan

ECG lifetime

100000 h

At Tcase = 65°C at Tc point / 10% failure rate

Additional product data

Suitable for lamp power (1 lamp)

14…39 W

Capabilities

Suitable for fixtures with prot. class

I / II

End of lamp life safety shutdown

EOL T.2

Intended for no-load operation

No

Dimmable

No

Max. cable length to lamp/LED module

2.0 m / 1.0 m

Certificates & standards

Approval marks – approval

VDE / VDE-EMC / ENEC 10 / CE

EEI – Energy Label

A2 BAT

Standards

Acc. to EN 61347-2-3/Acc. to EN 60929/Acc. to EN 55015:2006 + A1:2007/Acc. to EN 61000-3-2/Acc. to EN 61547

Type of protection

IP20

Protection class

II

Logistical data

Commodity code

85041080900

Environmental information


Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)

Date of Declaration

26-05-2023

Primary Article Identifier

4008321383334

Candidate List Substance 1

Lead

CAS No. of substance 1

7439-92-1

Safe Use Instruction

The identification of the Candidate List substance is sufficient to allow safe use of the article.

Declaration No. in SCIP database

d5c38eb8-c02d-4093-b57f-248b85a9b7da

Packaging information

EAN

Unit

Piece

Dimension l x w x h

Weight

Volume

4008321383334 UNV

Unpacked

1 360mm x 30mm x 21mm 210.00g 0.23dm³
4008321383341 VS

Shipping box

20 392mm x 165mm x 98mm 4425.00g 6.34dm³

Downloads

Lamp-ECG Combination
DULUX F 36 W

Nominal current

0.15 A

Nominal wattage + Power loss

34.00 W

Power factor λ [PIM]

0.96

Luminous flux at 35 °C

2750 lm

Number of lighting outlets

1

DULUX L 40 W

Nominal current

0.19 A

Nominal wattage + Power loss

44.00 W

Power factor λ [PIM]

0.98

Luminous flux at 35 °C

3500 lm

Number of lighting outlets

1

FC 22 W

Nominal current

0.15 A

Nominal wattage + Power loss

25.00 W

Power factor λ [PIM]

0.94 c

Luminous flux at 35 °C

1800 lm

Number of lighting outlets

1

FC 40 W

Nominal current

0.19 A

Nominal wattage + Power loss

43.00 W

Power factor λ [PIM]

0.96

Luminous flux at 35 °C

3200 lm

Number of lighting outlets

1

HE 14 W

Nominal current

0.08 A

Nominal wattage + Power loss

16.00 W

Power factor λ [PIM]

0.92 c

Luminous flux at 35 °C

1200 lm

Number of lighting outlets

1

ECG_1.1 Ambient temperature for lifespan

40 °C

ECG_1.2 Ambient temperature for lifespan

50 °C

ECG_1.3 Ambient temperature for lifespan

60 °C

ECG_2.1 Tc point temperature for lifespa

45 °C

ECG_2.2 Tc point temperature for lifespa

55 °C

ECG_2.3 Tc point temperature for lifespa

65 °C

ECG_3.1 Temperature dependent lifespan

100000 h

ECG_3.2 Temperature dependent lifespan

100000 h

ECG_3.3 Temperature dependent lifespan

100000 h

HE 21 W

Nominal current

0.11 A

Nominal wattage + Power loss

24.00 W

Power factor λ [PIM]

0.94 c

Luminous flux at 35 °C

1900 lm

Number of lighting outlets

1

ECG_1.1 Ambient temperature for lifespan

40 °C

ECG_1.2 Ambient temperature for lifespan

50 °C

ECG_1.3 Ambient temperature for lifespan

60 °C

ECG_2.1 Tc point temperature for lifespa

45 °C

ECG_2.2 Tc point temperature for lifespa

55 °C

ECG_2.3 Tc point temperature for lifespa

65 °C

ECG_3.1 Temperature dependent lifespan

100000 h

ECG_3.2 Temperature dependent lifespan

100000 h

ECG_3.3 Temperature dependent lifespan

100000 h

HE 35 W

Nominal current

0.18 A

Nominal wattage + Power loss

39.00 W

Power factor λ [PIM]

0.97

Luminous flux at 35 °C

3300 lm

Number of lighting outlets

1

HO 24 W

Nominal current

0.12 A

Nominal wattage + Power loss

26.00 W

Power factor λ [PIM]

0.96

Luminous flux at 35 °C

1750 lm

Number of lighting outlets

1

ECG_1.1 Ambient temperature for lifespan

40 °C

ECG_1.2 Ambient temperature for lifespan

50 °C

ECG_1.3 Ambient temperature for lifespan

60 °C

ECG_2.1 Tc point temperature for lifespa

50 °C

ECG_2.2 Tc point temperature for lifespa

60 °C

ECG_2.3 Tc point temperature for lifespa

65 °C

ECG_3.1 Temperature dependent lifespan

100000 h

ECG_3.2 Temperature dependent lifespan

100000 h

ECG_3.3 Temperature dependent lifespan

90000 h

HO 39 W

Nominal current

0.18 A

Nominal wattage + Power loss

41.00 W

Power factor λ [PIM]

0.98

Luminous flux at 35 °C

3100 lm

Number of lighting outlets

1

ECG_1.1 Ambient temperature for lifespan

40 °C

ECG_1.2 Ambient temperature for lifespan

50 °C

ECG_1.3 Ambient temperature for lifespan

60 °C

ECG_2.1 Tc point temperature for lifespa

50 °C

ECG_2.2 Tc point temperature for lifespa

60 °C

ECG_2.3 Tc point temperature for lifespa

65 °C

ECG_3.1 Temperature dependent lifespan

100000 h

ECG_3.2 Temperature dependent lifespan

100000 h

ECG_3.3 Temperature dependent lifespan

80000 h

L 18 W

Nominal current

0.09 A

Nominal wattage + Power loss

19.00 W

Power factor λ [PIM]

0.93 c

Luminous flux at 35 °C

1350 lm

Number of lighting outlets

1

L 36 W

Nominal current

0.09 A

Nominal wattage + Power loss

35.00 W

Power factor λ [PIM]

0.96

Luminous flux at 35 °C

3350 lm

Number of lighting outlets

1

L 38 W

Nominal current

0.09 A

Nominal wattage + Power loss

35.00 W

Power factor λ [PIM]

0.96

Luminous flux at 35 °C

3300 lm

Number of lighting outlets

1

Information about Family

If you want to upgrade or create a light installation with T5 lamps, the QUICKTRONIC INTELLIGENT ECG may be ideal for your project. It features lamp start with optimum filament preheating, along with automatic shutoff of defective lamps and at the end of life. Supply voltage is 220…240 V and line voltage is 198…264 V. This is an ECG that you can use with emergency lighting systems to EN 50172 / DIN VDE 0108-100, and with luminaires of protection classes I and II. It is great for industrial lighting, open plan office lighting, strip lighting and in sports halls and factories, and you can use it as a replacement ECG when you modernize existing systems. The QUICKTRONIC INTELLIGENT ECG is very robust and can withstand frequent on / off switching, it also provides perfect lamp start for applications with motion sensors, and automatic restart after lamp replacement.
Product family features
  • Supply voltage: 220…240 V
  • Line voltage: 198…264 V
  • Line frequency: 0 Hz | 50 Hz | 60 Hz
  • Lamp start with optimum filament preheating
  • Lifetime: > 100,000 h (for T = 65 °C at Tc)
  • Energy Efficiency Index EEI: A2 BAT
  • Automatic shutdown of defective lamps and at end of life (EoL T.2)
  • Safety: to EN 61347-2-3
  • Lamp operation: to EN 60929
Ecodesign regulation information:
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.

Products

Sort by:
Product
Height
Dimmable
ECG lifetime
Length
Width
Data sheet
QTi 1X14/24/21/39 GII
21.0 mm No 100000 h 360.0 mm 30.0 mm
QTi 1X28/54/35/49 GII
21.0 mm No 100000 h 360.0 mm 30.0 mm
QTi 1X35/49/80 GII
21.0 mm No 100000 h 360.0 mm 30.0 mm
QTi 2X14/24/21/39 GII
21.0 mm No 100000 h 360.0 mm 30.0 mm
QTi 2X28/54/35/49 GII
21.0 mm No 100000 h 360.0 mm 30.0 mm
QTi 2X35/49/80 GII
21.0 mm No 100000 h 424.0 mm 30.0 mm