QTi 2X28/54/35/49 GII
- Long lamp life
- No adverse effect from frequent on/off switching
- Automatic restart after lamp replacement
- Perfect lamp start for applications with motion sensors
- VDE/VDE EMC certified system
- Very high energy efficiency due to cut-off technology
- Emergency lighting systems acc. to EN 50172 / DIN VDE 0108-100
- Industry
- Open-plan offices, corridors and storage rooms
- Public buildings
- Sports halls and factories
- Strip lighting
- Suitable for emergency lighting (DC operation)
- Modernization of existing systems
- Suitable for luminaires of protection classes I and II
Technical Data
Electrical data
Input voltage AC
198 264 V
Nominal voltage
220 240 V
Mains frequency
50 60 Hz
Input voltage DC
176 276 V
Maximum output power
2 x 54 W
Efficiency in full-load
94 %
Operating frequency
42 85 kHz
Max. ECG no. on circuit breaker 10 A (B)
8
Max. ECG no. on circuit breaker 16 A (B)
13
Inrush current
53 A
Light technical data
Starting time
1.0 s
Dimensions & weight
Length
360.0 mm
Width
30.0 mm
Height
21.0 mm
Mounting hole spacing, length
350.0 mm
Product weight
270.00 g
Temperatures & operating conditions
Ambient temperature range
-20 +50 °C
Permitted rel. humidity during operation
5 85 %
Lifespan
ECG lifetime
100000 h
Additional product data
Suitable for lamp power (2 lamps)
28 54 W
Capabilities
End of lamp life safety shutdown
EOL T.2
Suitable for fixtures with prot. class
I / II
Intended for no-load operation
No
Max. cable length to lamp/LED module
2.0 m / 1.0 m
Dimmable
No
Certificates & standards
Approval marks approval
VDE / VDE-EMC / CE / ENEC 10
EEI Energy Label
A2 BAT
Standards
Acc. to EN 61347-2-3/Acc. to EN 60929/Acc. to EN 55015:2006 + A1:2007/Acc. to EN 61000-3-2/Acc. to EN 61547
Type of protection
IP20
Protection class
II
Logistical data
Commodity code
85041080900
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
26-05-2023
Primary Article Identifier
4008321383419
Candidate List Substance 1
Lead
CAS No. of substance 1
7439-92-1
Safe Use Instruction
The identification of the Candidate List substance is sufficient to allow safe use of the article.
Declaration No. in SCIP database
457f26e7-f122-422c-9564-8c2e84a71cc2
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4008321383419 |
UNV
| 1 | 360mm x 30mm x 21mm | 270.00g | 0.23dm³ |
4008321383426 |
VS
| 20 | 392mm x 98mm x 165mm | 5619.99g | 6.34dm³ |
Downloads
Data sheets
Lamp-ECG Combination
HE 14 W
Nominal current
0.15 A
Nominal wattage + Power loss
32.00 W
Power factor λ [PIM]
0.93 c
Luminous flux at 35 °C
1275 lm
Number of lighting outlets
2
HE 21 W
Nominal current
0.20 A
Nominal wattage + Power loss
45.00 W
Power factor λ [PIM]
0.96
Luminous flux at 35 °C
1900 lm
Number of lighting outlets
2
HE 28 W
Nominal current
0.28 A
Nominal wattage + Power loss
61.00 W
Power factor λ [PIM]
0.96
Luminous flux at 35 °C
2600 lm
Number of lighting outlets
2
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
55 °C
ECG_2.2 Tc point temperature for lifespa
60 °C
ECG_2.3 Tc point temperature for lifespa
70 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
100000 h
ECG_3.3 Temperature dependent lifespan
80000 h
HE 35 W
Nominal current
0.35 A
Nominal wattage + Power loss
76.00 W
Power factor λ [PIM]
0.96
Luminous flux at 35 °C
3300 lm
Number of lighting outlets
2
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
55 °C
ECG_2.2 Tc point temperature for lifespa
65 °C
ECG_2.3 Tc point temperature for lifespa
70 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
100000 h
ECG_3.3 Temperature dependent lifespan
70000 h
HO 49 W
Nominal current
0.46 A
Nominal wattage + Power loss
105.00 W
Power factor λ [PIM]
0.98
Luminous flux at 35 °C
4300 lm
Number of lighting outlets
2
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
55 °C
ECG_2.2 Tc point temperature for lifespa
65 °C
ECG_2.3 Tc point temperature for lifespa
70 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
100000 h
ECG_3.3 Temperature dependent lifespan
70000 h
HO 54 W
Nominal current
0.51 A
Nominal wattage + Power loss
115.00 W
Power factor λ [PIM]
0.98
Luminous flux at 35 °C
4450 lm
Number of lighting outlets
2
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
59 °C
ECG_2.1 Tc point temperature for lifespa
60 °C
ECG_2.2 Tc point temperature for lifespa
70 °C
ECG_2.3 Tc point temperature for lifespa
75 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
100000 h
ECG_3.3 Temperature dependent lifespan
50000 h
L 58 W
Nominal current
0.47 A
Nominal wattage + Power loss
109.00 W
Power factor λ [PIM]
0.99
Luminous flux at 35 °C
5000 lm
Number of lighting outlets
2
Information about Family
- Supply voltage: 220 240 V
- Line voltage: 198 264 V
- Line frequency: 0 Hz | 50 Hz | 60 Hz
- Lamp start with optimum filament preheating
- Lifetime: > 100,000 h (for T = 65 °C at Tc)
- Energy Efficiency Index EEI: A2 BAT
- Automatic shutdown of defective lamps and at end of life (EoL T.2)
- Safety: to EN 61347-2-3
- Lamp operation: to EN 60929
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|---|
![]() |
QTi 1X14/24/21/39 GII
|
21.0 mm | No | 100000 h | 360.0 mm | 30.0 mm | ||
![]() |
QTi 1X28/54/35/49 GII
|
21.0 mm | No | 100000 h | 360.0 mm | 30.0 mm | ||
![]() |
QTi 1X35/49/80 GII
|
21.0 mm | No | 100000 h | 360.0 mm | 30.0 mm | ||
![]() |
QTi 2X14/24/21/39 GII
|
21.0 mm | No | 100000 h | 360.0 mm | 30.0 mm | ||
![]() |
QTi 2X28/54/35/49 GII
|
21.0 mm | No | 100000 h | 360.0 mm | 30.0 mm | ||
![]() |
QTi 2X35/49/80 GII
|
21.0 mm | No | 100000 h | 424.0 mm | 30.0 mm |