QTP-M 2X26 32
Product family benefits
- Long lamp life
- No adverse effect from frequent on/off switching
- Automatic restart after lamp replacement
- Perfect lamp start for applications with motion sensors
- Separate installations thanks to optional cable clamp for K2 and K3 casings
- VDE/VDE EMC certified system
Areas of application
- Public buildings
- Sports halls and factories
- Suitable for luminaires of protection class I
Technical Data
Electrical data
Input voltage AC
198 264 V
Nominal voltage
220 240 V
Mains frequency
50 60 Hz
Input voltage DC
176 276 V
Maximum output power
2 x 32 W
Efficiency in full-load
93 %
Operating frequency
45 kHz
Max. ECG no. on circuit breaker 10 A (B)
11
Max. ECG no. on circuit breaker 16 A (B)
19
Line current
0.30 A
Inrush current
25 A
Light technical data
Starting time
1.0 s
Dimensions & weight
Length
123.0 mm
Width
79.0 mm
Height
33.0 mm
Mounting hole spacing, length
111.0 mm
Product weight
180.00 g
Cable cross-section, input side
0.5 1.5 mm²
Cable cross-section, output side
0.5 1.5 mm²
Temperatures & operating conditions
Ambient temperature range
-20 +50 °C
Permitted rel. humidity during operation
5 85 %
Lifespan
ECG lifetime
50000 h
Additional product data
Product remark
Optional cable clamp, see chapter ECG mountings - cable clamp
Suitable for lamp power (2 lamps)
26 32 W
Capabilities
End of lamp life safety shutdown
EOL T.2
Suitable for fixtures with prot. class
I / II
Dimmable
No
Max. cable length to lamp/LED module
2.0 m / 1.0 m
Intended for no-load operation
No
Certificates & standards
Approval marks approval
VDE / VDE-EMC / ENEC 10 / GOST / RCM
EEI Energy Label
A2
Standards
Acc. to EN 61347-2-3/Acc. to EN 60929/Acc. to EN 55015:2006 + A1:2007/Acc. to EN 61000-3-2/Acc. to EN 61547
Protection class
III
Type of protection
IP20
Logistical data
Commodity code
85041080900
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
28-04-2023
Primary Article Identifier
4008321329158
Candidate List Substance 1
Lead
CAS No. of substance 1
7439-92-1
Safe Use Instruction
The identification of the Candidate List substance is sufficient to allow safe use of the article.
Declaration No. in SCIP database
dc7d562f-b5f3-4425-b1d4-eeac0769ceaf
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4008321329158 |
UNV
| 1 | |||
4008321329165 |
VS
| 20 | 418mm x 255mm x 82mm | 3839.00g | 8.74dm³ |
Downloads
Lamp-ECG Combination
DULUX D/E 26 W
DULUX F 18 W
DULUX F 24 W
DULUX F 36 W
DULUX L 18 W
DULUX L 24 W
DULUX L 36 W
DULUX T/E 26 W
DULUX T/E 32 W
DULUX T/E 42 W
FC 22 W
HO 24 W
Information about Family
QUICKTRONIC MULTIWATT ECG is designed for use with compact fluorescent lamps and comes in a choice of three variants, so you can select precisely the version you need for your professional lighting project. It features lamp start with optimum filament preheating and has an energy efficiency index of A2. Use it with luminaires of protection class I in public buildings, sports halls and industrial lighting applications such as factories. This ECG gives you perfect lamp start in applications using motion sensors, no adverse effects from frequent on/off switching and you can install it independently using the cable clamp for K2 and K3 casings.
Product family features
- Supply voltage: 220 240 V
- Line voltage: 198 264 V
- Line frequency: 0 Hz | 50 Hz | 60 Hz
- Lamp start with optimum filament preheating
- Energy Efficiency Index EEI: A2
- Automatic shutdown of defective lamps and at end of life (EoL T.2)
- Lamp operation: to EN 60929
- Safety: to EN 61347-2-3
Ecodesign regulation information:
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|---|
QT-M 2X26
42 S
|
33.0 mm | No | 50000 h | 123.0 mm | 79.0 mm | |||
QTP-M 1X26
42
|
31.0 mm | No | 50000 h | 103.0 mm | 67.0 mm | |||
QTP-M 2X26
32
|
33.0 mm | No | 50000 h | 123.0 mm | 79.0 mm |