QTP-OPTIMAL 2X54 58
Product family benefits
- Long lamp life
- No adverse effect from frequent on/off switching
- Automatic restart after lamp replacement
- Perfect lamp start for applications with motion sensors
- VDE/VDE EMC certified system
- Very high energy efficiency due to cut-off technology
Areas of application
- Emergency lighting systems acc. to EN 50172 / DIN VDE 0108-100
- Industry
- Open-plan offices, corridors and storage rooms
- Public buildings
- Sports halls and factories
- Strip lighting
- Suitable for emergency lighting (DC operation)
- Modernization of existing systems
- Suitable for luminaires of protection classes I and II
Technical Data
Electrical data
Input voltage AC
198 264 V
Nominal voltage
220 240 V
Mains frequency
50 60 Hz
Input voltage DC
176 276 V
Maximum output power
2 x 58 W
Efficiency in full-load
95 %
Operating frequency
40 50 kHz
Max. ECG no. on circuit breaker 10 A (B)
8
Max. ECG no. on circuit breaker 16 A (B)
13
Inrush current
57 A
Light technical data
Starting time
1.5 s
Dimensions & weight
Length
360.0 mm
Width
30.0 mm
Height
21.0 mm
Mounting hole spacing, length
350.0 mm
Product weight
239.90 g
Temperatures & operating conditions
Ambient temperature range
-20 +50 °C
Permitted rel. humidity during operation
5 85 %
Lifespan
ECG lifetime
100000 h
Additional product data
Suitable for lamp power (2 lamps)
54 58 W
Capabilities
Suitable for fixtures with prot. class
I / II
End of lamp life safety shutdown
EOL T.2
Suitable for emergency lighting
Yes
Intended for no-load operation
No
Dimmable
No
Max. cable length to lamp/LED module
2.0 m / 1.0 m
Certificates & standards
Approval marks approval
EL / VDE / ENEC 10 / VDE-EMC
EEI Energy Label
A2 BAT
Standards
Acc. to IEC 61347-2-3 / App. J/Acc. to EN 55015:2006 + A1:2007 + A2:2009/Acc. to EN 61000-3-2/Acc. to EN 61547
Type of protection
IP20
Protection class
I
Logistical data
Commodity code
850410809000
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
19-05-2023
Primary Article Identifier
4008321880253
Candidate List Substance 1
Lead
CAS No. of substance 1
7439-92-1
Safe Use Instruction
The identification of the Candidate List substance is sufficient to allow safe use of the article.
Declaration No. in SCIP database
53cefce3-b0c5-425e-9061-e9aa20b864e0
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4008321880253 |
UNV
| 1 | 253.00g | ||
4008321880260 |
VS
| 20 | 385mm x 160mm x 100mm | 5016.00g | 6.16dm³ |
Downloads
Data sheets
Lamp-ECG Combination
DULUX L 55 W
Nominal current
0.48 A
Nominal wattage + Power loss
110.00 W
Power factor λ [PIM]
0.99
Luminous flux at 35 °C
4800 lm
Number of lighting outlets
2
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
55 °C
ECG_2.2 Tc point temperature for lifespa
65 °C
ECG_2.3 Tc point temperature for lifespa
75 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
100000 h
ECG_3.3 Temperature dependent lifespan
60000 h
HO 54 W
Nominal current
0.52 A
Nominal wattage + Power loss
120.00 W
Power factor λ [PIM]
0.99
Luminous flux at 35 °C
4450 lm
Number of lighting outlets
2
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
60 °C
ECG_2.2 Tc point temperature for lifespa
65 °C
ECG_2.3 Tc point temperature for lifespa
75 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
90000 h
ECG_3.3 Temperature dependent lifespan
50000 h
L 58 W
Nominal current
0.49 A
Nominal wattage + Power loss
112.00 W
Power factor λ [PIM]
0.99
Luminous flux at 35 °C
5000 lm
Number of lighting outlets
2
ECG_1.1 Ambient temperature for lifespan
40 °C
ECG_1.2 Ambient temperature for lifespan
50 °C
ECG_1.3 Ambient temperature for lifespan
60 °C
ECG_2.1 Tc point temperature for lifespa
55 °C
ECG_2.2 Tc point temperature for lifespa
65 °C
ECG_2.3 Tc point temperature for lifespa
75 °C
ECG_3.1 Temperature dependent lifespan
100000 h
ECG_3.2 Temperature dependent lifespan
100000 h
ECG_3.3 Temperature dependent lifespan
60000 h
NS 55W G13
Information about Family
QUICKTRONIC PROFESSIONAL OPTIMAL, available in several variants, is a great option if your professional lighting installation includes fluorescent lamps and / or compact fluorescent lamps. This high performance, energy efficient ECG gives you lamp start with optimum filament preheating, auto shutdown of failed lamps and at end of life, and can be used for emergency lighting (DC operation). Use it with luminaires of protection classes I and II for open plan office lighting, strip lighting, public buildings, sports halls and industrial lighting including factories. You can also use it for ECG installation in the modernization of existing systems. Benefits of the QUICKTRONIC PROFESSIONAL OPTIMAL include long lamp life, the ability to withstand frequent on / off switching, auto restart after lamp replacement and perfect lamp start for systems with motion sensors. Its cutoff technology makes this ECG highly energy efficient.
Product family features
- Supply voltage: 220 240 V
- Line voltage: 198 264 V
- Line frequency: 0 Hz | 50 Hz | 60 Hz
- Lamp start with optimum filament preheating
- Lifetime: up to 100,000 h (temperature at Tc = 65 °C, max. 10 % failure rate)
- Energy Efficiency Index EEI: A2 BAT
- Automatic shutdown of defective lamps and at end of life (EoL T.2)
- Safety: to EN 61347-2-3
- Lamp operation: to EN 60929
Ecodesign regulation information:
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|---|
![]() |
QTP-OPTIMAL 1X18
40
|
21.0 mm | No | 100000 h | 280.0 mm | 30.0 mm | ||
![]() |
QTP-OPTIMAL 1X54
58
|
21.0 mm | No | 100000 h | 280.0 mm | 30.0 mm | ||
![]() |
QTP-OPTIMAL 2X18
40
|
21.0 mm | No | 100000 h | 360.0 mm | 30.0 mm | ||
![]() |
QTP-OPTIMAL 2X54
58
|
21.0 mm | No | 100000 h | 360.0 mm | 30.0 mm |