OT 200/ 220-240/1A4 2DIM P7
- Easily programmable by NFC (AstroDIM / Constant lumen)
- High surge protection: up to 10 kV
- High efficiency
- Lifetime: up to 100,000 h
- Street and urban lighting
- Industry lighting
- Suitable for luminaires of protection class I
Technical Data
Electrical data
Nominal voltage
220 240 V
Input voltage AC
198 264 V
Nominal current
1 A
Mains frequency
50 60 Hz
Power factor λ
≥ 095
Total harmonic distortion
< 10 %
Device power loss
17 W
Inrush current
98 A
Max. ECG no. on circuit breaker 10 A (B)
3
Max. ECG no. on circuit breaker 16 A (B)
5
Max. ECG no. on circuit breaker 25 A (B)
7
Surge capability (L/N-Ground)
10 kV
Surge capability (L-N)
6 kV
Nominal output power
100 200 W
Maximum output power
200 W
Efficiency in full-load
92 %
Nominal output current
700 1400 mA
Default output current
700 mA
Output current tolerance
±5 %
Output ripple current (100 Hz)
< ±5 %
Minimum output current
400 mA
Galvanic isolation
basic
U-OUT (working voltage)
350 V
Nominal output voltage
121...286 V
Dimensions & weight
Length
2284 mm
Width
685 mm
Height
396 mm
Mounting hole spacing, length
215.6 mm
Mounting hole spacing, width
42.9 mm
Product weight
100000 g
Cable cross-section, input side
1.0 mm²
Cable cross-section, output side
1.0 mm²
Wire preparation length, input side
10 mm
Cable/wire length, output side
300±20 mm
Cable/wire length, control input
220±20 mm
Wire preparation length, output side
10 mm
Cable/wire length, input side
590±20 mm
Colors & materials
Casing material
Aluminium
Temperatures & operating conditions
Ambient temperature range
-40 +55 °C
Temperature range at storage
-40 +85 °C
Maximum temperature at tc test point
90 °C
Max.housing temperature in case of fault
120 °C
Permitted rel. humidity during operation
5 95 %
Lifespan
ECG lifetime
50000 / 100000 h
Capabilities
Dimmable
Yes
Dimming interface
AstroDIM / 1 10 V / Pulse Width Modulation
Dimming range
10 100 %
Suitable for fixtures with prot. class
I
Constant lumen function
Yes
NTC input
No
Short-circuit protection
Automatic reversible
No-load proof
Automatic reversible
Intended for no-load operation
No
Max. cable length to lamp/LED module
2.0 m
Overload protection
Automatic reversible
Number of channels
1
Programming
Tuner4TRONIC
Yes
Programming device
NFC
Certificates & standards
Type of protection
IP67
Standards
Acc. to EN 61347-1/Acc. to EN 61347-2-13/Acc. to EN 55015/Acc. to EN 61547/Acc. to EN 61000-3-2/Acc. to EN 61000-3-3/Acc. to EN 62384/EN 60598-1(ED.8)
Approval marks approval
CE / CCC / RCM / ENEC 05 / TISI
Logistical data
Commodity code
85044083900
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
26-10-2023
Primary Article Identifier
4062172069649
Candidate List Substance 1
Lead
CAS No. of substance 1
7439-92-1
Safe Use Instruction
The identification of the Candidate List substance is sufficient to allow safe use of the article.
Declaration No. in SCIP database
31d9d9d9-be37-472c-b1d5-4744d09a3f5b
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4062172069649 |
UNV
| 1 | 228mm x 69mm x 40mm | 1000.00g | 0.62dm³ |
4062172069656 |
VS
| 10 | 495mm x 309mm x 130mm | 10994.00g | 19.88dm³ |
Downloads
Information about Family
- 2DIM functionality (AstroDIM, 1 10 V)
- Wide output current range
- Adjustable and Constant Lumen Output (CLO)
- Short-circuit, overload and overtemperature protection
- High IP protection (IP67)
- 1 10 V dimming (minimum 10%)
Intended for use with LED modules.
The forward voltage of the LED light source shall be within the defined operating window of the control gear in all operating conditions including dimming if applicable.
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|
OT 100/ 220-240/1A4 2DIM P7
|
700 1400 mA | 1644 mm | 685 mm | 396 mm | |||
OT 150/ 220-240/1A4 2DIM P7
|
700 1400 mA | 2034 mm | 685 mm | 396 mm | |||
OT 200/ 220-240/1A4 2DIM P7
|
700 1400 mA | 2284 mm | 685 mm | 396 mm | |||
OT 240/ 220-240/1A0 2DIM P7
|
700...1050 mA | 2524 mm | 685 mm | 396 mm |