OTI DX 50/220...240/1A4 NFC
- Versatile DALI window driver due to flexible output characteristic
- Integrated DEXAL Bus power supply for sensors and wireless radios
- Simplified luminaire design for wireless lighting control system and sensors
- Locking and unlocking of luminaire/driver data
- Advanced luminaire/driver data (power, energy, operating hours ) for analytics
- D4i certified incl. Parts 250, 251, 252, 253
- Easy and fast output current setting via NFC
- Very high efficiency
- High-quality dimming of 1 100 % by amplitude dimming
- Suitable for emergency Installations (acc. to EN 60598-2-22 and IEC 61347-2-13,appendix J) thanks to DC detection (0 Hz, pulsating DC), on/off switchable
- Feedback of power consumption and operating hours (Fit for SMART GRID)
- Suitable for buildings according to EPBD/BREEAM/LEED due to automatic Constant Lumen Output setting
- DEXAL, easy connection to different partner BMS systems
- Suitable for "Works with OSRAM DEXAL" partner components
- Installation in emergency lighting systems according to IEC 61347-2-13, appendix J
- Suitable for use in luminaires with flexible current setting
- Suitable for indoor SELV installations
- Suitable for luminaires of protection classes I and II
- Suitable for downlights, spotlights and LED panels
- Installation via Cable Clamp Kit possible (depending on version of product)
Technical Data
Electrical data
Nominal input voltage
220 240 V
Mains frequency
0/50/60 Hz
Input voltage AC
198 264 V
Input voltage DC
176 276 V
Total harmonic distortion
< 10 %
Power factor λ
083C 098
Efficiency in full-load
91 %
Device power loss
6.2 W
Inrush current
30 A
Max. ECG no. on circuit breaker 10 A (B)
12
Max. ECG no. on circuit breaker 10 A (C)
-
Max. ECG no. on circuit breaker 16 A (C)
-
Max. ECG no. on circuit breaker 16 A (B)
20
Max. ECG no. on circuit breaker 25 A (B)
-
Surge capability (L/N-Ground)
2 kV
Surge capability (L-N)
1 kV
Nominal output voltage
15 54 V
U-OUT (working voltage)
60 V
Nominal output current
600 1400 mA
Default output current
1050 mA
Output current tolerance
±3 %
Output ripple current (100 Hz)
< 3 %
Output PSTLM
≤1
Output SVM
≤0.4
Nominal output power
55 W
Maximum output power
55 W
DEXAL Supply Voltage
15 V
DEXAL Peak Supply Current
60 mA
DEXAL Guaranteed Supply Current
53 mA
Power loss in stand-by mode
<0.15 W
Galvanic isolation DALI/mains
SELV
Galvanic isolation DALI/output
SELV
Networked standby power
≤0.15 W
Current set
DALI / NFC
Galvanic isolation primary/secondary
SELV
Dimensions & weight
Mounting hole spacing, length
99.0 mm
Mounting hole spacing, width
64.0 mm
Product weight
18500 g
Cable cross-section, input side
0.2 1.5 mm²
Cable cross-section, output side
0.2 1.5 mm²
Wire preparation length, input side
8.0 9.0 mm
Wire preparation length, output side
8.0 9.0 mm
Width
750 mm
Length
1100 mm
Height
250 mm
Colors & materials
Casing material
Plastic
Temperatures & operating conditions
Ambient temperature range
-20 +50 °C
Maximum temperature at tc test point
80 °C
Max.housing temperature in case of fault
110 °C
Temperature range at storage
-40 +85 °C
Permitted rel. humidity during operation
5 85 %
Lifespan
ECG lifetime
50000 / 100000 h
Capabilities
Dimmable
Yes
Dimming interface
DALI-2 / DEXAL / D4i
Dimming range
1 100 %
Dimming method
Amplitude Modulation
Overheating protection
Automatic reversible
Overload protection
Automatic reversible
Short-circuit protection
Automatic reversible
No-load proof
Yes
Intended for no-load operation
No
Max. cable length to lamp/LED module
2.0 m
Suitable for fixtures with prot. class
I / II
Type of connection, input side
Push terminal
Type of connection, output side
Push terminal
Constant lumen function
Programmable
Suitable for through-wiring
Yes with optional cable clamp
DALI-2 Energy Data
Yes
Programming interface
DALI, NFC
Number of channels
1
DALI-2 Diagnostic Data
Yes
Programming
Box programming
Yes
Tuner4TRONIC
Yes
Programming device
DALI / NFC
Tuner4TRONIC Field App
Yes
Programmable features
Emergency Mode
Yes
DALI-2 Luminaire Data
Yes
Configuration Lock
Yes
Soft Switch Off
Yes
Operating Current
Yes
Dim to Dark
Yes
TouchDIM + Sensor
No
Corridor Functionality
No
OEM Key
No
Constant Lumen
Yes
Lamp Operating Time
Yes
Driver Guard
Yes
DALI Settings
Yes
Certificates & standards
Approval marks approval
ENEC 10 / VDE / EMC / EL / CE / DALI-2 / CCC / EAC / D4i
Standards
Acc. to EN 61347-1/Acc. to EN 61347-2-13/Acc. to EN 55015/Acc. to EN 61547/Acc. to EN 61000-3-2/Acc. to EN 62384/Acc. to EN 62386/Acc. to IEC 62386-101:Ed2/Acc. to IEC 62386-102:Ed2/Acc. to IEC 62386-207:Ed1/Acc. to IEC 62386-250/Acc. to IEC 62386-251, -252, -253
Protection class
II
Type of protection
IP20
Logistical data
Commodity code
85044083900
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
14-07-2023
Primary Article Identifier
4062172061865
Candidate List Substance 1
Lead
CAS No. of substance 1
7439-92-1
Safe Use Instruction
The identification of the Candidate List substance is sufficient to allow safe use of the article.
Declaration No. in SCIP database
a0369a02-b942-498c-9dd5-e3789afa536a
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4062172061865 |
UNV
| 1 | 167.00g | ||
4062172061872 |
VS
| 20 | 389mm x 234mm x 72mm | 4218.00g | 6.55dm³ |
Downloads
Accessories optional
Information about Family
This device has a DEXAL interface and is fully digitally programmable by NFC and DALI with integrated luminaire info and data monitoring DiiA -251, -252, -253. It is also available with a cable clamp for independent installations and through-looping. DALI dimming of 1 100% is also possible.
- Supply voltage: 220 240 V
- Line frequency: 0 Hz | 50 Hz | 60 Hz
- Line voltage: 198 264 V
- According to EN 61347-1, 61347-2-13, 62384
- RI suppression: to EN 55015/CISPR 15
- Immunity according to EN 61547
- Lifetime: up to 100,000 h
- Type of protection: IP20
Intended for use with LED modules.
The forward voltage of the LED light source shall be within the defined operating window of the control gear in all operating conditions including dimming if applicable.
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|---|
OTI DX 25/220
240/700 NFC
|
15 54 V | 180 700 mA | 1030 mm | 670 mm | 295 mm | |||
OTI DX 35/220
240/1A0 NFC
|
15 54 V | 350 1050 mA | 1030 mm | 670 mm | 295 mm | |||
OTI DX 50/220...240/1A4 NFC
|
15 54 V | 600 1400 mA | 1100 mm | 750 mm | 250 mm |