PTi 150/220 240 I
- Extended terminal section enables mains looping
- Screw-down cable clamps for reliable strain relief
- Long reliable life at maximum permitted temperatures
- Automatic safety shutdown of lamps in the event of a defect or at end of life (EoL)
- Shop lighting
- Health and fitness areas (in luminaires with protection class IP66 or higher)
- Effect and accent lighting
Safety advice
Ballast losses and lamp heat radiation can lead to heat accumulation in a completely closed case. Therefore it is necessary to ensure that the temperature at the measuring point t of the ECG does not exceed the maximum value.
Attention!
For safety reasons disconnect the device before replacing the lamp!
Technical Data
Electrical data
Lamp wattage
147 W
Maximum output power
147 W
Line current
0.72 A
Ignition voltage
4.5 kVp
Operating frequency
0.165 kHz
System wattage
160.00 W
Efficiency in full-load
92 %
Input voltage AC
198 254 V
Nominal voltage
220 240 V
Mains frequency
50 60 Hz
Power factor λ
0.95
Inrush current
70 A
Max. ECG no. on circuit breaker 10 A (B)
4
Max. ECG no. on circuit breaker 16 A (B)
7
Max. no. of ECGs on 16A MCB with EBN-OS
17
Protective conductor current
0.4 mA
U-OUT (working voltage)
250 V
Max. working voltage between LH and LL
250 V
Max. working voltage betw. LL/LH & earth
250 V
Max. capacitance of wire ECG/lamp
120 pF
Dimensions & weight
Length
212.0 mm
Width
93.0 mm
Height
33.0 mm
Mounting hole spacing, length
203.0 mm
Cable cross-section, input side
0.75 2.5 mm²
Cable cross-section, output side
0.75 2.5 mm²
Wire preparation length, input side
10 11 mm
Wire preparation length, output side
10 11 mm
Product weight
420.00 g
Colors & materials
Casing material
Plastic
Temperatures & operating conditions
Ambient temperature range
-25 +50 °C
Maximum temperature at tc test point
75 °C
Lifespan
ECG lifetime
40000 h
Additional product data
Design / version
With cable clamp
Suitable for lamp power (1 lamp)
150 W
Capabilities
Max. cable length to lamp/LED module
1.5 m
Overheating protection
Power reduction and switch off at T > 75 °C at the tc point
ECG reset time
> 0.5 s
Cable/wire types, input side
NYM-J 3x1.5 / NYM-J 3x2.5 / H05VV-F 3x1.5 / NHXMH-J 3x1.5 mm²
Cable/wire types, output side
SIHF-J 3x1.5 / SIHF-J 3x2.5 / SIHSI 3x1.0 mm²
Dimmable
No
Restriction on ignition time
20 min
Suitable for fixtures with prot. class
I
Intended for no-load operation
No
Certificates & standards
Approval marks approval
ENEC 10 / VDE / VDE-EMC / EAC / C-Tick
Type of protection
IP20
EEI Energy Label
A2
Standards
Acc. to EN 61347-2-12/Acc. to EN 55015/Acc. to EN 61000-3-2/Acc. to EN 61547/Acc. to EN 61347-2-12/Acc. to EN 62493
Logistical data
Commodity code
850410809000
Environmental information
Information according Art. 33 of EU Regulation (EC) 1907/2006 (REACh)
Date of Declaration
26-05-2023
Primary Article Identifier
4008321915535
Candidate List Substance 1
Lead
CAS No. of substance 1
7439-92-1
Safe Use Instruction
The identification of the Candidate List substance is sufficient to allow safe use of the article.
Declaration No. in SCIP database
8ab6db02-47b2-4112-8211-db4ec755751b
Packaging information
EAN |
Unit |
Piece |
Dimension l x w x h |
Weight |
Volume |
---|---|---|---|---|---|
4008321915535 |
UNV
| 1 | 212mm x 93mm x 33mm | 420.00g | 0.65dm³ |
4008321915542 |
VS
| 20 | 488mm x 100mm x 453mm | 9440.00g | 22.11dm³ |
Downloads
Data sheets
Lamp-ECG Combination
HQI-T 150W
HQI-TS 150W
Information about Family
- Energy Efficiency Index EEI: A2
- Supply voltage: 220 240 V
- Line frequency: 50 60 Hz
- RI suppression: to EN 55015/CISPR 15
- Safety: to EN 61347-2-12
- Line harmonics according to EN 61000-3-2
- Immunity according to EN 61547
Separate control gear and light sources must be disposed of at certified disposal companies in accordance with Directive 2012/19/EU (WEEE) in the EU and with Waste Electrical and Electronic Equipment (WEEE) Regulations 2013 in the UK. For this purpose, collection points for recycling centres and take-back systems (CRSO) are available from retailers or private disposal companies, which accept separate control gear and light sources free of charge. In this way, raw materials are conserved and materials are recycled.
Products
Product |
|
|
|
|
|
Data sheet | ||
---|---|---|---|---|---|---|---|---|
![]() |
PTi 35/220
240 I
|
32.0 mm | 171.0 mm | 220 240 V | 39 W | 4.5 kVp | ||
![]() |
PTi 70/220
240 I
|
32.0 mm | 171.0 mm | 220 240 V | 73 W | 4.5 kVp | ||
![]() |
PTi 150/220
240 I
|
33.0 mm | 212.0 mm | 220 240 V | 147 W | 4.5 kVp |